Washington § 70.74.050 - Quantity and distance table for explosives manufacturing buildings.

Full text of Washington Revised Code of Washington § 70.74.050 — Quantity and distance table for explosives manufacturing buildings., with citation guidance and answers to common questions.

§ 70.74.050. Quantity and distance table for explosives manufacturing buildings.

All explosives manufacturing buildings shall be located one from the other and from other buildings on explosives manufacturing plants in which persons are regularly employed, and all magazines shall be located from factory buildings and buildings on explosives plants in which persons are regularly employed, in conformity with the intraexplosives plant quantity and distance table below set forth:
 
 
 
 
 
 
EXPLOSIVES
 
Pounds
Over
Pounds
Not Over
Distance
Feet
 
 
 
Separate
Building or
Within
Substantial
Dividing Walls
. . . .
 
10
 
 
 
10
 
25
 
40
 
25
 
50
 
60
 
50
 
100
 
80
 
100
 
200
 
100
 
200
 
300
 
120
 
300
 
400
 
130
 
400
 
500
 
140
 
500
 
750
 
160
 
750
 
1,000
 
180
 
1,000
 
1,500
 
210
 
1,500
 
2,000
 
230
 
2,000
 
3,000
 
260
 
3,000
 
4,000
 
280
 
4,000
 
5,000
 
300
 
5,000
 
6,000
 
320
 
6,000
 
7,000
 
340
 
7,000
 
8,000
 
360
 
8,000
 
9,000
 
380
 
9,000
 
10,000
 
400
 
10,000
 
12,500
 
420
 
12,500
 
15,000
 
450
 
15,000
 
17,500
 
470
 
17,500
 
20,000
 
490
 
20,000
 
25,000
 
530
 
25,000
 
30,000
 
560
 
30,000
 
35,000
 
590
 
35,000
 
40,000
 
620
 
40,000
 
45,000
 
640
 
45,000
 
50,000
 
660
 
50,000
 
55,000
 
680
 
55,000
 
60,000
 
700
 
60,000
 
65,000
 
720
 
65,000
 
70,000
 
740
 
70,000
 
75,000
 
770
 
75,000
 
80,000
 
780
 
80,000
 
85,000
 
790
 
85,000
 
90,000
 
800
 
90,000
 
95,000
 
820
 
95,000
 
100,000
 
830
 
100,000
 
125,000
 
900
 
125,000
 
150,000
 
950
 
150,000
 
175,000
 
1,000
 
175,000
 
200,000
 
1,050
 
200,000
 
225,000
 
1,100
 
225,000
 
250,000
 
1,150
 
[ 1972 ex.s. c 88 s 8; 1931 c 111 s 5; RRS s 5440-5.]

Source: official Washington text · Last verified 2026-08-27

Frequently Asked Questions About Washington § 70.74.050

What does Revised Code of Washington § 70.74.050 cover?

Section 70.74.050 ("Quantity and distance table for explosives manufacturing buildings.") is part of the Revised Code of Washington, the codified statutory law of Washington. It sets out the legal rule or procedure described in the text above. Statutes are amended regularly, so always verify against the official source.

How do I cite Washington § 70.74.050?

A common citation format is "Revised Code of Washington § 70.74.050" (Washington). Legal writing may require the code abbreviation, section number, and year or edition. Match the style required by your court, professor, or publisher.

Is this the official text of Washington law?

No. This page is for research and education and may not include the most recent amendments. For official current law, check the Washington official source linked on this page or consult a licensed Washington attorney.

How does Washington § 70.74.050 apply to my situation?

Statutes are interpreted in context, and application depends on your specific facts. Only a licensed attorney in Washington can advise on how this section applies to you. Contact your state or local bar association for a referral.

Sources & Verification

Not legal advice. Verify against the official source and consult a licensed attorney in Washington.