Nevada § 477.150 - Fire sprinklers; elevators; posting of floor numbers and route for evacuation; heating, ventilating, air-conditioning and paging systems

Full text of Nevada Nevada Revised Statutes § 477.150 — Fire sprinklers; elevators; posting of floor numbers and route for evacuation; heating, ventilating, air-conditioning and paging systems, with citation guidance and answers to common questions.

§ 477.150. Fire sprinklers; elevators; posting of floor numbers and route for evacuation; heating, ventilating, air-conditioning and paging systems

The owner or operator of every hotel, motel, office, apartment building or condominium

where human occupancy is permitted on floors which are more than 55 feet above the

lowest level of ground accessible to vehicles of a fire department, shall: 1. Equip each exit corridor of the building with fire sprinklers as required by regulations

of the State Fire Marshal; 2. Except in a condominium, equip each room with at least one fire sprinkler above

each door opening into an exit corridor of the building; 3. Equip every elevator so as to permit it to be recalled automatically, in compliance

with section A 17.1 of the 1978 edition of the American National Standards Institute

and section 211.3 of the 1981 amendments to that edition, to the first floor or, if

necessary, to any other floor of the building not affected by fire; 4. Post the number of each floor in every stairwell and in every lobby adjacent to

an elevator; 5. Equip the heating, ventilating and air-conditioning system with an automatic device

to shut it off as prescribed in section 1009 of the 1979 edition of the Uniform Mechanical Code , and with an additional smoke detector as required by the 1978 edition of National

Fire Protection Association Standard 90A; and 6. In each room primarily used for sleeping, except in a condominium: (a) Post in a prominent location an explanation of the route to use for evacuation

of the building; and (b) Install a paging alarm system which conforms to the regulations of the State Fire

Marshal, to permit vocal warning and instructions to the occupants. 7. In a condominium, install in the common areas a paging alarm system meeting the

requirements of paragraph (b) of subsection 6, with a sound level of 80 decibels.

Source: official Nevada text · Last verified 2026-08-27

Frequently Asked Questions About Nevada § 477.150

What does Nevada Revised Statutes § 477.150 cover?

Section 477.150 ("Fire sprinklers; elevators; posting of floor numbers and route for evacuation; heating, ventilating, air-conditioning and paging systems") is part of the Nevada Revised Statutes, the codified statutory law of Nevada. It sets out the legal rule or procedure described in the text above. Statutes are amended regularly, so always verify against the official source.

How do I cite Nevada § 477.150?

A common citation format is "Nevada Revised Statutes § 477.150" (Nevada). Legal writing may require the code abbreviation, section number, and year or edition. Match the style required by your court, professor, or publisher.

Is this the official text of Nevada law?

No. This page is for research and education and may not include the most recent amendments. For official current law, check the Nevada official source linked on this page or consult a licensed Nevada attorney.

How does Nevada § 477.150 apply to my situation?

Statutes are interpreted in context, and application depends on your specific facts. Only a licensed attorney in Nevada can advise on how this section applies to you. Contact your state or local bar association for a referral.

Sources & Verification

Not legal advice. Verify against the official source and consult a licensed attorney in Nevada.