§ 125.1504j. Multiple-family dwelling; single interior exit stairway; requirements.

Sec. 4j.

Subject to section 4k, a multiple-family dwelling that has not more than 4 levels above grade plane may have a single interior exit stairway if all of the following conditions are met:

(a) The dwelling has not more than 4 units on each level.

(b) The net floor area of each level of the dwelling is not more than 4,000 square feet.

(c) The exit access travel distance is not more than 125 feet measured from the most remote point within a level of the dwelling along the natural and unobstructed path of egress travel.

(d) Openings to the interior exit stairway enclosure are limited to all of the following openings:

(i) Openings required for exit access into the enclosure from normally occupied spaces.

(ii) Openings required for egress from the enclosure.

(iii) Openings to the exterior.

(e) An elevator does not open into the interior exit stairway enclosure.

(f) The dwelling has a manual fire alarm system and an automatic smoke detection system that activates an occupant notification system. The manual fire alarm system, automatic smoke detection system, and occupant notification system all must be installed in accordance with the building code.

(g) Smoke detectors are located in common spaces outside of the dwelling units, including, but not limited to, all of the following areas:

(i) Gathering areas.

(ii) Laundry rooms.

(iii) Mechanical equipment rooms.

(iv) Storage rooms.

(v) Interior corridors.

(vi) Interior exit stairways.

(vii) Exit passageways.

(h) Regardless of the stairway construction type in the dwelling, automatic sprinkler locations in the interior exit stairway comply with the requirements for combustible stairways under the "Standard for the Installation of Sprinkler Systems", as adopted by the director as part of the code, developed by the National Fire Protection Association. If a standard described in this subdivision is revised after the effective date of the amendatory act that added this section, the department shall take notice of the revision and the department shall promulgate rules to incorporate the revision by reference.

(i) An electrical receptacle is not located in an interior exit stairway.

(j) The interior exit stairway is not less than 48 inches wide.

Source: official Michigan text · Last verified 2026-08-27

Frequently Asked Questions About Michigan § 125.1504j

What does Michigan Compiled Laws § 125.1504j cover?

Section 125.1504j ("Multiple-family dwelling; single interior exit stairway; requirements.") is part of the Michigan Compiled Laws, the codified statutory law of Michigan. It sets out the legal rule or procedure described in the text above. Statutes are amended regularly, so always verify against the official source.

How do I cite Michigan § 125.1504j?

A common citation format is "Michigan Compiled Laws § 125.1504j" (Michigan). Legal writing may require the code abbreviation, section number, and year or edition. Match the style required by your court, professor, or publisher.

Is this the official text of Michigan law?

No. This page is for research and education and may not include the most recent amendments. For official current law, check the Michigan official source linked on this page or consult a licensed Michigan attorney.

How does Michigan § 125.1504j apply to my situation?

Statutes are interpreted in context, and application depends on your specific facts. Only a licensed attorney in Michigan can advise on how this section applies to you. Contact your state or local bar association for a referral.

Sources & Verification

Not legal advice. Verify against the official source and consult a licensed attorney in Michigan.